Parameter Details
12
12.5 d: References
YASKAWA SIEPC71061753C GA500 Technical Manual 581
Figure 12.60 shows the Offset frequency function:
Figure 12.60 Offset Frequency Operation
d7-01: Offset Frequency 1
No.
(Hex.)
Name Description
Default
(Range)
d7-01
(02B2)
RUN
Offset Frequency 1
Uses H1-xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)] as a percentage of
the Maximum Output Frequency to add or subtract the set frequency to/from the frequency
reference.
0.0%
(-100.0 - +100.0%)
d7-02: Offset Frequency 2
No.
(Hex.)
Name Description
Default
(Range)
d7-02
(02B3)
RUN
Offset Frequency 2
Uses H1-xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)] as a percentage of
the Maximum Output Frequency to add or subtract the set frequency to/from the frequency
reference.
0.0%
(-100.0 - +100.0%)
d7-03: Offset Frequency 3
No.
(Hex.)
Name Description
Default
(Range)
d7-03
(02B4)
RUN
Offset Frequency 3
Uses H1-xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)] as a percentage of
the Maximum Output Frequency to add or subtract the set frequency to/from the frequency
reference.
0.0%
(-100.0 - +100.0%)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals