Parameter Details
12
12.8 H: Terminal Function Selection
YASKAWA SIEPC71061753C GA500 Technical Manual 675
Figure 12.95 Stall Prevention Level during Run with Analog Input
9: Output Frequency Lower Limit
Setting Value Function Description
9 Output Frequency Lower
Limit
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.
B: PID Feedback
Setting Value Function Description
B PID Feedback
Enter the PID feedback value as a percentage of the maximum output frequency.
When you use this function, set b5-01 = 1 to 8 [PID Mode Setting = Enabled].
C: PID Setpoint
Setting Value Function Description
C PID Setpoint
Enters the PID setpoint as a percentage of the maximum output frequency.
When you use this function, set b5-01 = 1 to 8 [PID Mode Setting = Enabled].
Note:
Configuring this function disables the frequency reference set with b1-01 [Frequency Reference Selection 1].
D: Frequency Bias
Setting Value Function Description
D Frequency Bias
Enters the bias value added to the frequency reference as a percentage of the maximum output frequency.
The drive adds the input value from the MFAI terminal set with this function to the frequency reference as the bias
value.
Note:
When you select d1-01 to d1-16 or d1-17 [Reference 1 to 16 or JOG Frequency Reference] as the frequency reference, it will disable
this function.
E: Motor Temperature (PTC Input)
Setting Value Function Description
E Motor Temperature (PTC
Input)
Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor as a percentage of the
current value when the 10 Vanalog signal is input.
You can use the Positive Temperature Coefficient (PTC) thermistor as an auxiliary or alternative detection
function for oL1 [Motor Overload] problems to help prevent heat damage to motors. If the PTC input signal is
more than the overload alarm level, oH3 [Motor Overheat (PTC Input)] will flash on the keypad.
When the drive detects oH3, the motor stops with the setting in L1-03. When the drive detects oH4, the motor
stops with the setting in L1-04. When the drive incorrectly detects motor overheating problems, set L1-05.
F: Not Used
Setting Value Function Description
F Not Used
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals