Option
Name
Description
[132]
Feedback 4–
20mA
[133]
Motor cur. 4–
20mA
The value is taken from parameter 16-37 Inv. Max. Current. The inverter maximum current (160%
current) is equal to 20 mA. Example: Inverter normal current (11 kW) is 24 A. 160% = 38.4 A. Motor
normal current is 22 A, the readout is 11.46 mA.
16mA × 22A
38 . 4A
 = 13 . 17mA
If the normal motor current is equal to 20 mA, the output setting of parameter 6-52 Terminal 42
Output Max Scale is:
IVLT, MAX × 100
IMotor, Nom
îš‹ = îš‹
38 . 4 × 100
22
 = 175 %
[134]
Torq.% lim 4–
20mA
The torque setting is related to the setting in parameter 4-16 Torque Limit Motor Mode.
[135]
Torq.% nom 4–
20mA
The torque setting is related to the motor torque setting.
[136]
Power 4–20mA
Taken from parameter 1-20 Motor Power [kW].
[137]
Speed 4–20mA
Taken from parameter 3-03 Maximum Reference. 20 mA = value in parameter 3-03 Maximum Refer-
ence.
[138]
Torque 4–20mA
Torque reference related to 160% torque.
[139]
Bus ctrl.
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[140]
Bus ctrl. 4–20mA
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[141]
Bus ctrl t.o.
Parameter 4-54 Warning Reference Low defines the behavior of the analog output in case of field-
bus timeout.
[142]
Bus ctrl 4-20mA
t.o.
Parameter 4-54 Warning Reference Low defines the behavior of the analog output in case of field-
bus timeout.
[147]
Main act val
[148]
Main act val
4-20mA
[149]
Torque % lim
4-20mA
Analog output at 0 torque is 12 mA. Motoring torque increases the output current to maximum
torque limit 20 mA (set in parameter 4-16 Torque Limit Motor Mode). Generating torque decreases
the output to torque limit in generator mode (set in parameter 4-17 Torque Limit Generator Mode)
Example: Parameter 4-16 Torque Limit Motor Mode = 200% and parameter 4-17 Torque Limit Genera-
tor Mode = 200%. 20 mA = 200% motoring and 4 mA = 200% generating.
[150]
Max Out Fr
4-20mA
0 Hz = 0 mA, parameter 4-19 Max Output Frequency = 20 mA.
[158]
Motor Volt.
[159]
Motor Volt.
4-20mA
AU275636650261en-000101 / 130R0334 | 251Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals