Parameter 6-81 Terminal X45/3 Min. Scale
Table 442: Parameter 6-81 Terminal X45/3 Min. Scale
6-81 Terminal X45/3 Min. Scale
Default value: 0%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Scales the minimum output of the selected analog signal on terminal X45/3. Scale the minimum value as a percentage of the maxi-
mum signal value, for example, 0 mA (or 0 Hz) is required at 25% of the maximum output value and 25% is programmed. The value
can never exceed the corresponding setting in parameter 6-82 Terminal X45/3 Max. Scale if the value is below 100%. This parameter
is active when VLT® Extended Relay Card MCB 113 is mounted in the drive.
Parameter 6-82 Terminal X45/3 Max. Scale
Table 443: Parameter 6-82 Terminal X45/3 Max. Scale
6-82 Terminal X45/3 Max. Scale
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Scale the maximum output of the selected analog signal at terminal X45/3. Set the value to the maximum value of the current signal
output. Scale the output to give a current lower than 20 mA at full scale, or 20 mA at an output below 100% of the maximum signal
value. If 20 mA is the required output current at a value between 0–100% of the full-scale output, program the percentage value in
the parameter, for example 50% = 20 mA. If a current 4–20 mA is required at maximum output (100%), calculate the percentage
value as follows (example where required maximum output is 10 mA):
IRANGEîš‹ mA
IDESIREDMAX mA
 × 100 %
=
20−4mA
10mA
 × 100 %  = 160 %
Parameter 6-83 Terminal X45/3 Bus Control
Table 444: Parameter 6-83 Terminal X45/3 Bus Control
6-83 Terminal X45/3 Bus Control
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: -2
Data type: N2
Change during operation: True
Holds the level of analog output 4 (terminal X45/3) if controlled by bus.
Parameter 6-84 Terminal X45/3 Output Timeout Preset
Table 445: Parameter 6-84 Terminal X45/3 Output Timeout Preset
6-84 Terminal X45/3 Output Timeout Preset
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: 1 setup
Conversion index: -2
Data type: Uint16
Change during operation: True
Holds the preset level of output 4 (X45/3). If there is a fieldbus timeout and a timeout function is selected in parameter 6-80 Terminal
X45/3 Output, the output is preset to this level.
AU275636650261en-000101 / 130R0334252 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals