Table 563: Parameter 9-70 Edit Set-up
Default value: [1] Set-up 1
Change during operation: True
Select the setup in which programming (change of data) is performed during operation. It is possible to program the 2 setups inde-
pendently of the setup selected as the active setup. Parameter access from each master is directed to the setup selected by the
individual master (cyclic, acyclic MCL1, 1
st
acyclic MCL2, 2
nd
acyclic MCL2, 3
rd
acyclic MCL2).
Parameter 9-71 PROFIBUS Save Data Values
Table 564: Parameter 9-71 PROFIBUS Save Data Values
9-71 PROFIBUS Save Data Values
Change during operation: True
Parameter values changed via RS485 are not automatically stored in a non-volatile memory. Use this parameter to activate a func-
tion that stores parameter values in the EEPROM non-volatile memory, so changed parameter values are retained at power-down.
Parameter 9-72 PROFIBUSDriveReset
Table 565: Parameter 9-72 PROFIBUSDriveReset
Default value: [0] No action
Change during operation: False
N O T I C E
Resets the VLT® PROFIBUS DP-V1 MCA 101 option only.