Type 05010M:
Metering
mode Display
Metering
output
100 %
(V)
Max. stroke
frequency
at 100%
(¦)
Stroke
volume
(V
h
)
Suction
stroke
Duration
(S
t
)
min. metering
stroke
duration
(P
t
)
Standard
54 l/h 159 / min
5,8 ml
185 ms
192 ms
Medium 45 l/h 145 / min 222 ms
Low 36 l/h 114 / min 333 ms
Variable
27 - 54 l/h 107 - 159 / min 370 - 185 ms
Type 12003M:
Metering
mode Display
Metering
output
100 %
(V)
Max. stroke
frequency
at 100%
(¦)
Stroke
volume
(V
h
)
Suction
stroke
Duration
(S
t
)
min. metering
stroke
duration
(P
t
)
Standard 120 l/h 148 / min
13.5 ml
200 ms
205 ms
Medium
100 l/h 135 / min 240 ms
Low 80 l/h 106 / min 360 ms
Variable 60 - 120 l/h 99 - 148 / min 400 - 200 ms
Switching between the metering modes means that the diaphragm
metering pump must be re-calibrated!
The calibration symbol C! is displayed on the display of the operating level.
Once the automatic [Calibration]
has been correctly carried out, the symbol
C! is hidden in the operating level again!
The table values displayed for the max. stroke frequency (max. metering
capacity) are dependent on the pump size and calibration.
The details about the suction stroke and metering stroke times are
theoretical values. They may vary according to calibration tolerances,
suction line lengths, back-pressure, etc.
Control / software
69 Rev. 2-05.2018

Table of Contents

Other manuals for Ecolab EcoAdd

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ecolab EcoAdd and is the answer not in the manual?

Ecolab EcoAdd Specifications

General IconGeneral
BrandEcolab
ModelEcoAdd
CategoryWater Pump
LanguageEnglish

Related product manuals