User Manual Section 4
GFK-2958L May 2021
Detailed Descriptions of the Fieldbus Network Adapters 127
4.5.7 Status word EPXEIP001(Packed process data input)
Summarized module diagnosis
A diagnosis is available for at least one module with diagnostics
functionality.
Reserve bit 1, currently not used
Reserve bit 2, currently not used
Error on the system bus. Communication with the connected
modules is disrupted.
Unacknowledged diagnosis alarm
Unacknowledged diagnosis alarm
Unacknowledged process alarm
Unacknowledged process alarm
Deviation in the configuration. The module list has changed. The list
of configured modules (Configured Module
Ident List class 0x65 (101), instance 0x01 (1), attribute 0x70 (112))
differs from the module list detected
by the adapter (Detected Module Ident List class 0x65 (101),
instance 0x01 (1), attribute 0x6F (111)).
Master configuration error
Master configuration error. The list of configured modules
(Configured Module Ident List class 0x65 (101),
instance 0x01, attribute 0x70 (112)) differs significantly from the
module list detected by the adapter
(Detected Module Ident List class 0x65 (101), instance 0x01 (1),
attribute 0x6F (111)) ab. No process data
can be exchanged with the modules.
Reserve bit 8, currently not used
Reserve bit 9, currently not used
Force mode was activated through the web server. Process data
cannot be exchanged between the master
and forced channels.
Reserve bit 11, currently not used
Reserve bit 12, currently not used
Error in the voltage supply of output current path
Error in the voltage supply of system and input current path
Reserve bit 15, currently not used