User Manual Section 5
GFK-2958L May 2021
Detailed Description of I/O Modules 322
5.27.3 Modifiable Parameters for EP-3124
Channel
Description
Options
Default
Frequency suppression
disabled (0) /
50 Hz (1) /
60 Hz (2) /
Average over 16 values (3)
disabled
0 ... 3
Measurement range
0 to 20 mA (0) /
4 to 20 mA (1) /
0 V to 10 V (2) /
-10 to 10 V (3) /
0 to 5 V (4) /
-5 to 5 V (5) /
1 to 5 V (6) /
2 to 10 V (7) /
disabled (8)
disabled
5.27.4 Diagnostic Data EP-3124
Name
Bytes
Bit
Description
Default
Error indicator
0
0
Module error
1
Internal error
2
External error
3
Channel error
0
4
Error
5
Reserved
0
6
Reserved
0
7
Parameter error
Module type
1
0
Module Type
0x05
1
2
3
4
Reserved
0
5
Reserved
0
6
Reserved
0
7
Reserved
0
Error byte 2
2
0-7
Reserved
0
Error byte 3
3
0-2
Reserved
0
3
Internal diagnostic FIFO full
4
Power supply fault
5
Reserved
0
6
Reserved
0
7
Reserved
0
Channel type
4
0-6
Channel type
0x74
7
Reserved
0
Diagnostic bits
per channel
5
Number of diagnostic bits per
channel
0
Number of
channels
6
Number of similar channels
per module
4

Table of Contents

Other manuals for Emerson PACSystems RSTi-EP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson PACSystems RSTi-EP and is the answer not in the manual?

Emerson PACSystems RSTi-EP Specifications

General IconGeneral
BrandEmerson
ModelPACSystems RSTi-EP
CategoryController
LanguageEnglish

Related product manuals