User Manual Section 5
GFK-2958L May 2021
Detailed Description of I/O Modules 157
5.5.2 Specifications EP-125F
Specification
Description
System data
Data
Process, parameter and diagnostic data depend on the network
adapter used (refer to Section 3.1Order and Arrangement of
Modules
Interface
RSTi-EP I/O communication bus
System bus transfer rate
48 Mbps
Inputs
Number
16
Sensor types
Type 1 and Type 3 sensors as per IEC 61131-2
Input filter
Input delay 3ms
Low input voltage
< 5 V
High input voltage
> 11 V
Sensor supply
No
Sensor connection
1-conductor
Reverse polarity protection
Yes
Module diagnosis
Yes
Individual channel diagnosis
No
Supply
Supply voltage
20.4V 28.8V
Current consumption from system current path
ISYS
8 mA
Current consumption from input current path IIN
52 mA
General data
Weight
87 g (3.07 oz)
5.5.3 Diagnostic Data EP-125F
Name
Bytes
Bit
Description
Default
Error indicator
0
0
Module error
1
Internal error
2
External error
3
Channel error
0
4
Error
5
Reserved
0
6
Reserved
0
7
Parameter error
Module type
1
0
Module Type
0x0F
1
2
3
4
Reserved
0
5
Reserved
0
6
Reserved
0

Table of Contents

Other manuals for Emerson PACSystems RSTi-EP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson PACSystems RSTi-EP and is the answer not in the manual?

Emerson PACSystems RSTi-EP Specifications

General IconGeneral
BrandEmerson
ModelPACSystems RSTi-EP
CategoryController
LanguageEnglish

Related product manuals