User Manual Section 5
GFK-2958L May 2021
Detailed Description of I/O Modules 351
5.32.2 Specifications EP-3704
Process, parameter and diagnostic data depend on the
network adapter used (refer to Section, Order and
Arrangement of Modules).
RSTi-EP I/O communication bus
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni 200, Ni500,
Ni1000, Cu10, 40 Ω, 80 Ω, 150 Ω, 300 Ω, 500 Ω, 1 kΩ, 2
kΩ, 4 kΩ
max. 0.2 % FSR /
0.3 % FSR for Ni sensors /
0.6 % FSR for Cu10
depending on the sensor type 0.75 mA (Pt100, Ni100,
Ni120, Cu10, 40 Ω, 80 Ω, 150 Ω, 300 Ω) or 0.25 mA
(Pt200, Pt500, Pt1000, Ni200, Ni500, Ni1000, 500 Ω,
1 kΩ, 2 kΩ, 4 kΩ)
Max. wire resistance / measurement range
2.5 Ω / 40 Ω, 5 Ω / 80 Ω, 10 Ω / 150 Ω and Cu10,
25 Ω in all other measuring ranges
-200 to +850°C (-328 to 1562 °F)
Common mode input voltage range
Channel to channel: max. ±2 V
Channel to voltage supply: max. ±50 V
Reverse polarity protection
Individual channel diagnosis
Current consumption from system current path ISYS,
Current consumption from input current path IIN
For additional general data, refer to Section,
General Technical Data for I/O Modules.