User Manual Section 5
GFK-2958L May 2021
Detailed Description of I/O Modules 348
Measurement
range
Current (I) /
Voltage (U)
Decimal (D)
Hexadecimal
Range
Conversion
0 5 V
5.25 V
29030
0x7166
Overloading
D = 27648 x U/5
I = D x 5 / 27648
5 V
27648
0x6C00
Nominal range
2.5 V
13824
0x3600
0 V
0
0x0000
±5 V
5.25 V
29376
0x72C0
Overloading
D = 27648 x (U 1) / 4
U = (D x 4 / 27648) + 1
5 V
27648
0x6C00
Nominal range
2.5 V
13824
0x3600
0 V
0
0x0000
-2.5 V
-13824
0xCA00
-5 V
-27648
0x9400
-5.25 V
-43200
0x5740
Underloading
† If the process value is beyond the valid value range, the corresponding channel releases 0 V and 0 mA respectively
The following applies for all ranges:
value > overload range = output deactivated
value < underload range = output deactivated