Note
-
When
designing
environmental
control
systems
such
as
air
conditioning
facilities,
confirm
that
the
air
taken
in
by
each
chassis
meets
the
requirements
specified
in
this
section.
Table
2-5
  
Environmental
conditions
Item In
operation Not
in
operation Optimal
condition
Ambient
temperature
5°C
to
35°C
41°F
to
95°F
-
When
unpacked
0
to
50
(32
to
122
)
-
When
still
packed
-25
to
60
(-4
to
140
)
21°C
to
23°C
70°F
to
74°F
Relative
humidity
(*1)
-
When
installed
in
server
room
20%
RH
to
80%
RH
-
When
installed
in
office
(*2)
20%
RH
to
80%
RH
-
When
installed
in
server
room
8%
RH
to
80%
RH
-
When
installed
in
office
(*2)
8%
RH
to
80%
RH
Maximum
wet-bulb
temperature
-
When
installed
in
server
room
26°C
(78.8°F)
-
When
installed
in
office
(*2)
29°C
(84.2°F)
-
When
installed
in
server
room
27
(80.6
)
-
When
installed
in
office
(*2)
29°C
(84.2°F)
Altitude
limit
(*3)
0
m
to
3,000
m
(0
ft.
to
10,000
ft.)
0
m
to
12,000
m
(0
ft.
to
40,000
ft.)
2.5 Checking
Environmental
Conditions
This
section
describes
the
environmental
conditions
for
the
SPARC
M10
systems.
The
server
can
be
installed
at
locations
that
meet
the
environmental
conditions
listed
in
Table
2-5.
The
environmental
conditions
described
in
Table
2-5
reflect
test
results
from
each
chassis.
The
optimal
conditions
represent
the
recommended
environment
in
operation.
The
component
failure
rate
may
increase
substantially
when
the
system
operates
for
prolonged
periods
in
an
environment
that
is
at
or
close
to
the
operation-
time
(in
operation)
limit
values,
or
when
the
system
is
installed
in
an
environment
that
is
at
or
close
to
the
non-operation-time
(not
in
operation)
limit
values.
To
minimize
the
occurrence
of
system
downtime
due
to
a
component
failure,
set
the
temperature
and
humidity
within
the
optimal
condition
range.
 
The
following
conditions
must
be
met
to
prevent
overheating:
Neither
warm
air
nor
hot
air
blows
directly
on
the
front
of
the
rack
Neither
warm
air
nor
hot
air
blows
directly
on
the
front
panel
of
any
chassis
Fujitsu
M10/SPARC
M10
Systems
Installation
Guide
July
201538

Table of Contents

Other manuals for Fujitsu M10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu M10 and is the answer not in the manual?

Fujitsu M10 Specifications

General IconGeneral
BrandFujitsu
ModelM10
CategoryServer
LanguageEnglish

Related product manuals