11.11 SVCREQ 10: Read Folder Name
Use SVCREQ 10 to read the name of the currently-executing folder.
11.11.1 Output Parameter Block Format for SVCREQ
10
The output parameter block has a length of four words. It returns eight ASCII characters;
the last is a null character (00h). If the program name has fewer than seven characters,
null characters are added to the end.
Low Byte High Byte
address character 1 character 2
address + 1 character 3 character 4
address + 2 character 5 character 6
address + 3 character 7 0
11.11.2 Example of SVCREQ 10
In this example, when enabling input %I0301 goes OFF, register location %R0099 is
loaded with the value 10, which is the function code for the Read Folder Name function.
The Program Block READ_ID is then called to retrieve the folder name. The parameter
block is located at address %R0100.
%I0301
Program Block READ_ID
212 GFK-1503E VersaMax PLC User Manual