Modules Located in Single-ended Expansion Rack
The table below shows timing for modules located in a single-ended expansion rack with
a non-isolated Expansion Receiver module ((C200ERM002). This type of system does
NOT have an Expansion Transmitter module (IC200ETM001) in the main rack.
Module Type
CPU005/CPUE05 CPU001/CPU002
Local Single Rack Local Single Rack
Input Output Input Output
Discrete Input Type 1
â€
127
—
191
—
Discrete Input Type 2
â€
179
—
262
—
Discrete Output Type 1
â€
—
116
—
167
Discrete Output Type 2
â€
—
167
—
222
Discrete Output w/ ESCP
—
176
—
260
Per Point Fault Reporting
Intelligent Discrete Input 20 Points
643
—
763
—
Intelligent Discrete Output 12 Points
—
714
—
756
Analog Input 4 Channels
317
—
389
—
Analog Input 8 Channels
527
—
631
—
Analog Input 15 Channels
896
—
1054
—
Analog Output 2 Channels
—
204
—
266
Analog Output 4 Channels
—
296
—
374
Analog Output 8 Channels
—
480
—
592
Analog Output 12 Channels
—
664
—
809
Intelligent Analog Input 4 Channels
438
—
533
—
Intelligent Analog Input 7 Channels
479
—
580
—
Intelligent Analog Input 8 Channels
493
—
596
—
Intelligent Analog Output 4 Channels
—
484
—
613
PLC Network Comm Profibus-DP Slave
†††††††â€
DeviceNet Network Master/Slave
†††††††â€
â€
Mixed modules have both and input and output scan time values.
†â€
Network Communications Modules (NCM) Scan Impact Times vary depending upon the network
configuration.
Appendix A Performance Data GFK-1503E User Manual 311