EasyManuals Logo

Hitachi RCI User Manual

Hitachi RCI
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #217 background imageLoading...
Page #217 background image
Part Optional function
Indivi
dual
settin
g
Settings
Condition
setting
Description
H3
Operating mode change
restriction
O
00
Operating
mode change
disabled
(factory setting)
This function is used to configure
restrictions to the operating mode.
01
Operating
mode set by the
central control +
FAN mode
02
Unlimited
operating mode
H4
Operating modes for the
ventilation unit with
energy / heat recovery
O
00
Air conditioning
only
This function is only available for the
ventilation unit with energy / heat recovery.
01 Ventilation only
02
Air conditioning
+ ventilation
H5
Central control available
after forced stoppage
O
00 Not available
This function allows for central control after
the forced stoppage of the unit.
01 Available
O: allows for individual setting.
X: the setting is made for all outdoor units.
–: not used.
1
Setting 02 is not available on all indoor units.
2
On RPI units: 00 Increases speed 1 (standard), 01 Increases speed 2 (high static pressure), 02 Standard speed (low static
pressure).
3
00 standard (7-position setting); 01 draught prevention (cannot be set below two positions); 02 High ceilings (cannot be
set above two positions).
6.3.3 Description of the optional remote control functions
b1 – Elimination of the heating temperature offset
This function is useful when the thermistor is removed from the suction area of the indoor unit and installed somewhere
else. It is used when the temperature setting displayed on the remote control and the inlet air temperature of the indoor unit
are to be the same.
Settings
Actual temperature control
00 Standard setting. Selected temperature +4 °C increase
01 Offset elimination
02 Selected temperature +4 °C increase
b2 – Forced air circulation function on reaching the set temperature
This function is useful when the air in the room is stratified (hot air accumulates at the ceiling). Air stratification may occur
if LOW has been selected with the heating thermostat off. This function prevents air stratification in the room after stopping
the air conditioning system.
The circulation pump function maintains the fan speed, whether the thermostat is on or off. Hence, the air movement in the
room is kept at the same level to ensure even air distribution.
N O T E
If the indoor unit has an automatic louver, this function also remains active when the heating thermostat is switched
off.
6 Optional functions
205
SMGB0063 rev. 1 - 10/2010
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RCI and is the answer not in the manual?

Hitachi RCI Specifications

General IconGeneral
BrandHitachi
ModelRCI
CategoryAir Conditioner
LanguageEnglish

Related product manuals