EasyManuals Logo
Home>Honeywell>Control Panel>Notifier ID50

Honeywell Notifier ID50 User Manual

Honeywell Notifier ID50
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
ID50 Series Panel - Installation, Commissioning & Configuration Manual
Commissioning
33 997-263-000-11, Issue 11
January 2010
N
L
12
3
4
56
7
8910
11 1 2
13
14
15 16
ZONE FIRE
ZONE FIRE
ZONE FAULT
DISABLE/TEST
ZONE FAULT
DISABLE/TEST
00..9
31
4
2
46
7
5
[
98
MUTE BUZZER
RESET
EXTEND DELAY
END DELAY/
EVACUATE
SILENCE/
RESOUND
FIRE
DISABLEMENT
FAULT
TEST
POWER SUPPLY FAULT
EARTH FAULT
POWER
PLANT ALARM
FIRE OUTPUT ACTIVE
DELAYSACTIVE
FIRE OUTPUT:FAULT / DISABLED
FIRE CONTROL O/P: FAULT/ DISABLED
PRE- ALARM
SYSTEM FAULT
SOUNDER: FAULT/ DISABLED
4.5.2 Batteries
The ID50 Series Panel back box holds up to two 12V,
12Ah batteries. The batteries are not supplied with the
panel. A valve-regulated, lead-acid type MUST be used.
To avoid contact damage resulting from repeated
connection point arcing, it is recommended that the mains
is connected before the batteries.
To connect the batteries:
1 Externally isolate the mains supply at the third-party-
supplied isolation unit, remove the cover and fit the
batteries in the back box. If not done already, connect
the mains/battery/ supply wiring plug to the power
socket, between the transformer secondary fuse (FT1)
and the battery fuse (FC1).
2 Connect the red wire from the terminal block, TB2
(BAT+) to the positive terminal of battery 2 and the
black wire from the terminal block, TB2 (0V) to the
negative terminal on battery 1.
Connect one end of the interlink cable to battery 1
positive terminal only. DO NOT connect both ends of
the interlink cable at this stage.
3 Turn on the AC mains supply and verify that after
power-up:
i The panel indicates ‘CPU RESTART’.
ii The buzzer sounds.
iii The FAULT and SYSTEM FAULT LEDs illuminate.
4 Connect the interlink cable to the negative terminal
on battery 2.
5 Reset the panel and check that the LCD displays the
‘Status: NORMAL message and that the FAULT and
SYSTEM FAULT LEDs extinguish.
Battery Disposal
As a minimum, replace the batteries every four years.
Always dispose of the batteries in accordance with the
battery manufacturers recommendations and local
regulations.
Status: NORMAL
Sat 05/01/2002 00:00:00
CAUTION- ENERGY HAZARD!
NEVER short the battery
terminals.
2
4
5
TB2 (0 V)
Battery 1
TB2 (BAT +)
Battery 2
Battery
1
Battery
2
N
L
12
3
4
56
7
8910
11 12
13
14
15 16
ZONE FIRE
ZONE FIRE
ZONE FAULT
DISABLE/TEST
ZONE FAULT
DISABLE/TEST
00..9
31
4
2
46
7
5
[
98
MUTE BUZZER
RESET
EXTEND
DELAY
END DELAY/
EVACUATE
SILENCE/
RESOUND
FIRE
DISABLEMENT
FAULT
TEST
POWER SUPPLY FAULT
EARTH FAULT
POWER
PLANT ALARM
FIRE OUTPUT ACTIVE
DELAYSACTIVE
FIRE OUTPUT: FAULT / DISABLED
FIRE CONTROL O/P: FAULT/ DISABLED
PRE- ALARM
SYSTEM FAULT
SOUNDER: FAULT/ DISABLED
CAUTION- RISK OF EXPLOSION!
If battery is replaced with an
incorrect type.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID50 and is the answer not in the manual?

Honeywell Notifier ID50 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID50
CategoryControl Panel
LanguageEnglish

Related product manuals