ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
38
997-263-000-11, Issue 11
January 2010
MEMMEM
5.4 Level 3 Configuration Options
The Level 3 Configuration Options allow you to configure
the panel. These Options are listed in the menu map at
left. The default Level 3 passcode is given in
Appendix 1 - Specifications.
Before any configuration changes can be made, the memory
lock must be set to the unlocked position (see below).
Memory Lock Jumper Link
Jumper link J9 locks/unlocks the system configuration.
J9 is located to the left of terminal block TB8 (Digital / ÜE).
To configure the panel, J9 must be in the ‘unlocked’
position (link NOT fitted).
Fit the link to the jumper (J9) before returning to
normal operation.
Any attempt to access a configuration menu option while
the link is fitted will cause the following message to be
briefly displayed:
Memory is Locked!
J9J9
LOCKED
UNLOCKED