ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
86997-263-000-11, Issue 11
January 2010
5.7.3 Evacuation
The Evacuation option has two states, Yes (Y) and No
(N). This option is available with the Fire, Pre-Alarm and
Device Inputs rules. To change the Evacuation setting:
1 Press the ‘
3
’ button (using the numeric keypad) to
select the Evacuation option from the menu below.
2 Press the ‘
6
’ button to select the required setting.
Refer to Section 5.7, Control-By-Event Output
Rules for further information.
3 Confirm the selection by pressing the ‘
5
’ button. To
cancel the selection, press ‘
4
’ button. In either case
the menu below is re-displayed.
5.7.4 Silence
The Silence option has two states, Yes (Y) and No (N).
This option is available with the Fire, Pre-Alarm and
Device Inputs rules. To change the Silence setting from
the CBE Output Rules menu:
1 Using the numeric keypad, press ‘
4
’ to select the
Silence option from the menu below.
2 Press the ‘
6
’ button to select the required setting.
Refer to Section 5.7, Control-By-Event Output
Rules for further information.
3 Confirm the selection by pressing ‘
5
’. To cancel
the selection, press ‘
4
’ button. In either case the
menu below is re-displayed.
CBE Rule:01 1:Type 2:Filter 3:Evac
4:Silence 5:Interrupt ¦ : More
CBE Rule:01 Evacuate = [Y]
>:Change :Accept < : Cancel
CBE Rule:01 Evacuate = [N]
>:Change :Accept < : Cancel
CBE Rule:01 1:Type 2:Filter 3:Evac
4:Silence 5:Interrupt ¦ : More
CBE Rule:01 1:Type 2:Filter 3:Evac
4:Silence 5:Interrupt ¦ : More
CBE Rule:01 Silence = [N]
>:Change :Accept < : Cancel
CBE Rule:01 Silence = [Y]
>:Change :Accept < : Cancel
CBE Rule:01 1:Type 2:Filter 3:Evac
4:Silence 5:Interrupt ¦ : More
6
3
5
6
5
4