ID50 Series Panel - Installation, Commissioning & Configuration Manual
Introduction
3
997-263-000-11, Issue 11
January 2010
The EMC Directive 2004/108/EEC, by the application of
the following EMC Standards:
EN 61000-6-3: Electromagnetic Compatibility (EMC)
Generic emission standard for Residential,
Commercial and Light industrial environments
EN 50130-4: EMC Product family standard: Immunity
requirements for components of fire, intruder and
social alarm systems.
Low Voltage Directive 2006/95/EEC, by the application
of the safety standard:.
EN 60950-1: Safety of information technology
equipment.
The Construction Products Directive 89/106/EEC, by the
application of the following standards:
EN 54-2:1998, (Amd. 1 & 2): Fire detection and fire
alarm systems - Control and indicating equipment.
EN 54-4: 1998 (Amd. 1 & 2): Fire detection and fire
alarm systems - Power supply equipment.
1.5 EN54 Functions
This fire control panel is designed to comply with the
requirements of EN 54 Part 2/4. In addition to the basic
requirements of EN 54-2, the panel may be configured to
conform with the following optional functions - the applicable
clauses of EN 54-2 are referenced as follows:
Options Clause
Indications:
Fault signal from fire protection equipment 7.10.4
Recording of the number of entries
into fire alarm condition 7.13
Fault signals from points 8.3
Controls:
Delay to Outputs 7.11.1
Manual or automatic switching of delays to outputs 7.11.2
Dependency on more than one alarm signal, Type B 7.12.2
Disablement of each address point 9.5
Test condition 10
Outputs:
Fire alarm device(s) 7.8
Fire alarm routing equipment 7.9.1
Fire alarm routing equipment with alarm confimation 7.9.2
Automatic fire protection equipment: Type A 7.10.1
Automatic fire protection equipment: Type C 7.10.3
Fault warning routing equipment 8.9

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID50 and is the answer not in the manual?

Honeywell Notifier ID50 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID50
CategoryControl Panel
LanguageEnglish

Related product manuals