MAN0984_Iss 4_01/19 Touchpoint Plus
Pt. No. 3011M5001 24 Technical Handbook
3.2 Equipment Specification
3.2.1 Power Requirements (Controller Unit only)
The Touchpoint Plus system is designed to operate on a single phase, 50 to 60 Hz, 110/220 V~ (AC) supply with a
typical power consumption of less than 107 W.
Alternatively it can be connected to an 18 32 V (DC) supply with typical power consumption less than 107 W.
The system can contain an optional backup battery to guard against short-term power disruption.
8 ch, not including Field Device
power
Field Device power ( 8 ch* 5W)
Field Device power ( 4 ch* 5W)
Charging power for
backup battery
pack
When alarm devices are
connected
Table 1. Maximum Power Consumption Calculations
AC 110/220 V manually switchable
300 VAC surge for 5 sec without damage
110 150 % rated output power
27.6 32.4 VDC Hiccup mode, which recovers automatically when
the fault is removed.
Table 2. Power Supply (SMPS RS–150–24) Electrical Ratings