Long labels
Long labels having up to 64 characters can be given to devices and command builds. This is achieved by replacing commonly used words with token values (special codes). Tokenised labels :When
tokens are decoded, a trailing space is automatically added to the decoded word. Likewise when a label is beingtokenised, the word must have a space following it, or be at the end of a line. Therefore
a token word cannot be followed with a comma, dash or other such character.
To switch ON long labels: Press the Menu on/Off button -> [Test/Eng] -> [UserCode] -> enter your PIN (where necessary) -> <etc> -> [Config] -> <etc> -> [Label] -> [On] -> [Enter].
"
All tokenised labels are displayed in Upper case.
Banks 0, 1 and 2 show the list of tokens used by the software to reduce the character label to 32 characters or less.
Bank 0
General Building Features
AREA ANNEXE BLOCK BUILDING
CORE CORRIDOR DOOR DUCT
ENTRANCE ESCALATOR EXIT EXTENSION
FLAT HALL HOUSE LIFT
LOBBY RISER ROOM ROUTE
STAIRS TOWER UNIT VENTILATION
VOID ZONE
Vertical Location
LEVEL MEZZANINE FLOOR BASEMENT
GROUND FIRST SECOND THIRD
FOURTH CEILING ROOF ATRIUM
Geographic Location
NORTH SOUTH EAST WEST
NEAR OUTSIDE ABOVE UPPER
CENTRE LOWER LEFT RIGHT
FRONT REAR
Building Usage
ACCOMMODATION ADMIN BEDROOM BOILER
CENTRAL CHANGING COMPUTER CONTROL
CUPBOARD ELECTRICAL ENGINEERING EXTERNAL
Commissioning instructions
140 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Appendix C - Guidelines for standalone system commands