Single network without domain bridge Powering-up the Network
¨
Add one panel at a time starting from the network controller, adding one panel/node
at a time to side 1.
"
It can take a few minutes for the system map to update.
¨
For each panel powered-up the network controller will automatically try to establish
communication with the connected equipment.
¨
The network controller will display the status of the network as being started, secure
or non-secure and from now on will monitor and control the network
communications.
¨
Use disable comms to isolate a panel from the rest of the network, ie it operates at the
network card in an echo mode, select Menu On/Off -> [Control] -> [Disable] ->
[Comms] and enter the Network Card address, usually card 6.
How to check a Network map
¨
Using the Menu On/Off -> [Info] -> [Map] -> [NetMap] menu, enter the network
card address, usually card 6 and select [E].
The display will provide a list in cabling order the addresses of panels/nodes in the
networked system.
Here are examples of different networks. The lowest address ‘1’ is normally the
network controller.
Nodes on side 1 of a SECURE NETWORK
110424362227231
Nodes on side 1 of a NON-SECURE NETWORK
11042436
Nodes on side 2 of NON-SECURE NETWORK
1 23 7 22 2
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 91
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Single Vigilon Network
must all be set to the same
settings at all the panels / nodes in a single
networked system without domain bridge.
IO Card switches must be set to the Off
position. The network baud and domain
address switch are located on the DKC.
These switches
Node 1
Node 3
Node 2
Control panel
Network Card
Address 2
Baud 38.4K
Control panel
Network Card
Address 4
Baud 38.4K
Control panel
Network Card
Address 1
Baud 38.4K
Control panel
IO Card
all switches to
Off position
Network Card
Address 3
Baud 38.4K
Node 4
DKC
Address 1
Baud 19.2K
IO Card
all switches to
Off position
IO Card
all switches to
Off position
DKC
Address 1
Baud 19.2K
DKC
Address 1
Baud 19.2K
IO Card
all switches to
Off position
DKC
Address 1
Baud 19.2K

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Vigilon 4 loop and is the answer not in the manual?

Honeywell Vigilon 4 loop Specifications

General IconGeneral
BrandHoneywell
ModelVigilon 4 loop
CategoryControl Panel
LanguageEnglish

Related product manuals