Integral sounder operation
A sensor sounder device can have its integral sounder only actioned in the event of a local fire event being detected at the device.
¨
Integral sounder Sector operation (sometimes also called 'flag set' Sector) can be configured using the panel menu commands [SetUp]-> [Sector] -> [Sounder] -> [On]
¨
when a Sector is configured for 'integral sounder mode' then a fire event from a sensor sounder in the Sector will cause only the integral sounder to operate
¨
linked Sectors are not affected when sensor/sounder type device is triggered from Sector configured for 'integral operation mode', only its local sounder operates and fire is
reported at the panel
¨
Delay Blocks can be configured to action other Sectors from sector operating in an integral sounder mode
¨
Sectors configured for integral sounder mode operation can be setup to action command builds.
Commissioning instructions
144 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Appendix C - Guidelines for standalone system commands
SECTOR X
FLAG SET
ON
FLAG
SET OFF
DEFAULT
INTEGRAL
SOUNDER - ON
INTEGRAL
SOUNDER
OFF
(DEFAULT)
SECTOR X
OPERATION
DELAY
BLOCK
COMMAND
BUILD
ACTION
ACTION
SECTOR
This action is only applicable
if the was from afire non
Sensor Alarm device
The will operate normally when
actioned by another sector.
sector x
Setup
ONLY LOCAL
ALARM SOUNDS
NOTE: OTHER SENSOR SOUNDERS
IN AN `INTEGRAL SOUNDER SECTOR'
OPERATE IN A SIMILAR MANNER
ACTION
H
MCP
INTERFACE
SECTOR X
FIRE
H
MCP
INTERFACE
FIRE
Sensor
Alarm
device
Sensor
Alarm
device

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Vigilon 4 loop and is the answer not in the manual?

Honeywell Vigilon 4 loop Specifications

General IconGeneral
BrandHoneywell
ModelVigilon 4 loop
CategoryControl Panel
LanguageEnglish

Related product manuals