Parameterising analog modules
Parameter data
12
Parameter setting
12.3
12.3.1
l
12.3-4
EDSPM-TXXX-3.0-04/2004
Via the parameter data of the 4xanalog input / output module you can define the
following:
z
The signal function for each input or output (current metering, voltage
metering, temperature metering, or current signal output, voltage signal
output)
z
The module error behaviour
z
The conversion speed
For the 4xanalog input / output up to eight bytes of parameter data are available,
which are assigned via SDOs.
Depending on the plug-in station, the module is activated via the indices
I3001
h
... I3010
h
(max. 16 analog modules). The parameter data are assigned in
the subindex 1 ... 3.
epm-t194
Fig. 12.3-3 Display of the parameter data 4xanalog input /output
The following bytes with fixed assignment are available for parameter data:
Byte Assignment Lenze
setting
0 Activating/deactivating wire
Bit 0
Wire breakage detection for input E.0
00
h
breakage detection
1)
and
0 Deactivated
enabling/inhibiting diagnostic
1activated
E 12.3-6
alarm
Bit 1
Wire breakage detection for input E.1
0 Deactivated
1activated
E 12.3-6
Bits 2 ... 5 Reserved
Bit 6
0 Diagnostic alarm
inhibited
1 Diagnostic alarm
enabled
E 12.3-6
1 reser ved Bits 0 ... 7 Reserved
2 S e l e cting signal function for
input E.0
Selection of signal function E 12.3-13 3Bh
3 S e l e cting signal function for
input E.1
4 S e l e cting signal function for
output E.0
01
h
5
Selecting signal function for
output E.1
4xanalog input /output