Parameterising analog modules
Signal functions of 4xanalog input /output
12
Parameter setting
12.3
12.3.6
l
12.3-13
EDSPM-TXXX-3.0-04/2004
12.3.6 Signal functions of 4xanalog input / output
Note!
z
Short-circuit unused inputs (connect positive and negative
terminals) or deactivate them by assigning the function number
FF
h
.
z
In the event of an overflow or underflow, wrong values are
output. Strong signal jumps with sign reversal may occur.
Parameter
bytes 2/3
Signal function Signal range Format
1)
Tolerance
2)
00
h
5 Parameter da ta in module not overwritten
3Bh Voltage measuring ±10 V
-10.00
-16384
{0.01V}
{1
dec
}
+10.00
+16384
±0.2 % of the
final value
Lower range limit: -12.50 V
-20480
dec
B
Upper range limit: +12.50 V
+20480
dec
75
h
Voltage measuring 0 ... 10 V
0.00
0
{0.01V}
{1
dec
}
+10.00
+16384
±0.4 % of the
final value
Lower range limit: -
B
Upper range limit: +12.50 V
+20480
dec
28
h
Voltage measuring ±10 V
-10.00
-27648
{0.01V}
{1
dec
}
+10.00
+27648
±0.2 % of the
final value
Lower range limit: -11.76 V
-32512
dec
A
Upper range limit: +11.76 V
+32511
dec
7A
h
Voltage measuring 1 ... 5 V
+1.00
0
{0.01V}
{1
dec
}
+5.00
+27648
±0.6 % of the
final value
Lower range limit: 0.00 V
-6912
dec
A
Upper range limit: +5.704 V
+32511
dec
7D
h
Voltage measuring 0 ... 10 V
0.00
0
{0.01V}
{1
dec
}
+10.00
+27648
±0.4 % of the
final value
Lower range limit: -
Upper range limit: +11.76 V
+32511
dec
3A
h
Current measuring ±20 mA
-20.00
-16384
{0.01 mA}
{1
dec
}
+20.00
+16384
±0.3 % of the
final value
Lower range limit -25.00 mA
-20480
dec
B
Upper range limit: +25.00 mA
+20480
dec
76
h
Current measuring 0 ... 20 mA
0.00
0
{0.01 mA}
{1
dec
}
+20.00
+16384
±0.6 % of the
final value
Lower range limit -
B
Upper range limit:
+25.00 mA
+20480
dec
Input functions