Parameterising analog modules
Signal functions of 4xanalog output
12
Parameter setting
12.3
12.3.5
l
12.3-11
EDSPM-TXXX-3.0-04/2004
12.3.5 Signal functions of 4xanalog output
Note!
In the event of an overflow or underflow, wrong values are output.
Strong signal jumps with sign reversal may occur.
Parameter
bytes
2/3/4/5
Signal function Signal range Format
1)
Tolerance
2)
00
h
4 No signal emitted at output
01
h
Voltage signal output ±10 V
-10.00
-16384
{0.01V}
{1
dec
}
+10.00
16384
±0.2 %
Lower range limit: -11.85 V
-20480
dec
B
Upper range limit: +11.85 V
20480
dec
02
h
Voltage signal output +1 ... +5 V
1.0
0
{0.1V}
{1
dec
}
+5.0
16384
±0.05 %
Lower range limit: 0V
20480
dec
B
Upper range limit: +6.0 V
20480
dec
05
h
Voltage signal output 0 ... +10 V
0
0
{0.1V}
{1
dec
}
+10.0
16384
±0.2 %
Lower range limit: –
B
Upper range limit: +12.5 V
20480
dec
09
h
Voltage signal output ±10 V
-10.00
-27648
{0.01V}
{1
dec
}
+10.00 V
27648
dec
±0.05 %
Lower range limit: -11.85 V
-32767
dec
A
Upper range limit: +11.84 V
32767
dec
0A
h
Voltage signal output +1 ... +5 V
1.00
0
{0.01V}
{1
dec
}
+5.00
27648
±0.05 %
Lower range limit: 0V
-6912
dec
A
Upper range limit: +5.75 V
32767
dec
0D
h
Voltage signal output 0 ... +10 V
0
0
{0.1V}
{1
dec
}
+10.0
27648
±0.2 %
Lower range limit: –
Upper range limit: +11.5 V
32767
dec
03
h
Current signal output ±20 mA
-20.00
-16384
{0.01 mA}
{1
dec
}
+20.00
16384
±0.2 %
Lower range limit: -23.70 mA
-20480
dec
B
Upper range limit: +23.70 mA
+20480
dec
04
h
Current signal output 4 ... 20 mA
4.00
0
{0.01 mA}
{1
dec
}
20.00
16384
±0.2 %
Lower range limit: 0mA
-4096
dec
B
Upper range limit:
+23.70 mA
+20480
dec