Commissioning
Adjusting the motor
Motor temperature monitoring with KTY
6
6.6
6.6.4
6.6-11
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0594 MONIT SD6 3
0 TRIP
Activation of the motor
temperature monitoring with KTY
at X8
z UseC0594=0or2toactivate
monitoring
z In case of a short circuit or
interruption at X8/5 and X8/8
the fault message SD6 is
activated
z Configuration of the response
when exceeding the motor
temperature
– Fixed operating temperature
in C0583
– Variable operating
temperature in C0584
6.6-10
See System
Manual
(extension)
2 Warning
3 Off
Note!
ƒ In the Lenze setting, the motor temperature monitoring is
switched off!
ƒ If you work with several parameter sets, the monitoring must
be activated separately in each parameter set!
Use C0594 = 0 or C0594 = 2 to activate the motor temperature monitoring
via X8. In addition, the connection is monitored for short circuit and
interruption.
1. Connecting the monitoring circuit of the motor to X8/5 and X8/8.
2. Setting controller reaction to short circuit or interruption of the
connection:
– C0594 = 3: Monitoring is switched off.
– C0594 = 0: TRIP error message (display of keypad: Sd6 )
– C0594 = 2: Warning signal (display of keypad: Sd6 )
Monitoring with fixed operating temperature (150 °C)
1. Setting the controller reaction:
– C0583 = 3: Temperature monitoring of the motor is switched off.
– C0583 = 0: TRIP error message (display of keypad: OH3 )
Monitoring with variable operating temperature (45 ... 150 °C)
1. Setting the operating temperature in C0121.
2. Setting the controller reaction:
– C0584 = 3: Temperature monitoring of the motor is switched off.
– C0584 = 2: Warning signal (display of keypad: OH7 )
Activation