Technical data
Fuses and cable cross-sections
Mains supply
3
3.5
3.5.1
3.5-3
EDSVF9333V EN 3.0-06/2005
9300 vector Mains choke Operation with mains choke or mains filter
FI
2)
Type Mains Type
Installation according to EN 60204-1 or
VDE 0298-4
1)
Installation to UL
3)
c d
L1, L2, L3, PE
e L1, L2, L3, PE
EN 60204-1
Laying system
VDE 0298-4
Laying
system
b2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
EVF9321
3/PE AC
320 ... 528 V
45 ... 65 Hz
ELN3-0700H003 6 B6
C6
4)
1 1 – 5 18
300
EVF9322 ELN3-0700H003 6 B6
C6
4)
1 1 – 5 18
EVF9323 ELN3-0450H004 10 B10 1 1 – 5 18
EVF9324 ELN3-0250H007 10 B10 1.5 1 – 10 16
EVF9325 ELN3-0160H012 20 B20 4 4 – 20 12
EVF9326 ELN3-0120H025 35 B32 – 6 – 25 10
EVF9327 ELN3-0088H035 40 – 10 10 – 35 8
EVF9328 ELN3-0075H045 63 – 16 10 – 50 6
EVF9329 ELN3-0055H055 80 – – 25 – 80 4
EVF9330 ELN3-0038H085 100 – – 35 – 100 0
EVF9331 ELN3-0027H105 125 – – 70 50 125 0
EVF9332 ELN3-0022H130 160 – – 95 70 175 2/0
EVF9333 ELN3-0017H170 200 – – 120 95 200 3/0
c Fuse (fuses of utilisation category gG/gL or semiconductor fuses of utilisation category gRL)
d Circuit breaker
e Fuse
1)
The information represents recommendations. Other designs/laying systems are possible (e.g. to
VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated
copper leads, conductor temperature < 70 °C, ambient temperature < 40 °C, no bundling of cables
or cores, three loaded cores.
2)
Universal current sensitive earth-leakage circuit breaker
3)
Use only UL-approved cables, fuses and fuse holders. UL fuse: voltage 500 ... 600 V, tripping
characteristic ”H”, ”K5” or ”CC”.
4)
For short-time mains interruptions, use circuit breakers with tripping characteristic ”C”
National and regional regulations must be observed