Configuration
Code table
8
8.3
8.3-11
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0105 QSP Tif 5.00 0.00 {0.01 s} 999.90 Quick stop deceleration time
z The deceleration time refers to
a speed variation of C0011 ... 0
8.2-25
8.2-48
C0107 Holding time 0.00 0.00 {0.01 s} 9999.90 Hold time for automatic DC
injection braking (Auto-GSB)
8.2-25
8.2-48
C0108 -199.99 {0.01 %} 199.99 Free control code FCODE108/1
and FCODE108/2
6.5-6
See System
Manual
(extension)
1 FCODE (GAIN) 100.00 Gain of analog output signal
AOUT1 (X6/62)
z 100 % = gain 1
2 FCODE (GAIN) 100.00 Gain of analog output signal
AOUT2 (X6/63)
z 100 % = gain 1
C0109 -199.99 {0.01 %} 199.99 Free control code FCODE109/1
and FCODE109/2
1 FCODE (offset) 0.00 Offset of analog output signal
AOUT1 (X6/62)
2 FCODE (offset) 0.00 Offset of analog output signal
AOUT2 (X6/63)
C0114
0 High active HIGH level is
active
Inversion of digital input signals
at X5, function block DIGIN
6.5-1
See System
Manual
(extension)
1 LOW active LOW level is
active
1 DIGIN1 pol 0 Terminal X5/E1
2 DIGIN2 pol 0 Terminal X5/E2
3 DIGIN3 pol 0 Terminal X5/E3
4 DIGIN4 pol 1 Terminal X5/E4
5 DIGIN5 pol 0 Terminal X5/E5
5 DIGIN6 (ST) pol 0 Terminal X5/ST
C0116
Selection list 2
Configuration of free digital
outputs (FDO)
z Signals can only be evaluated
when being networked with
automation interfaced
See System
Manual
(extension)
1 CFG: FDO-0 1000 FIXED0
... ... ... ...
32 CFG: FDO-31 1000 FIXED0
C0117
Selection list 2 Configuration of digital inputs
signals, function block DIGOUT
A change of the basic
configuration in C0005 changes
the signal assignment!
6.5-3
See System
Manual
(extension)
1 CFG: DIGOUT1 15000 DCTRL-TRIP Terminal X5/A1
2 CFG: DIGOUT2 10650 CMP1-OUT Terminal X5/A2
3 CFG: DIGOUT3 500 DCTRL-RDY Terminal X5/A3
4 CFG: DIGOUT4 5003 MCTRL-MMAX Terminal X5/A4
C0118
0 High active HIGH level is
active
Inversion of digital output
signals, function block DIGOUT
1 LOW active LOW level is
active
1 DIGOUT1 pol 1 Terminal X5/A1
2 DIGOUT2 pol 1 Terminal X5/A2
3 DIGOUT3 pol 0 Terminal X5/A3
4 DIGOUT4 pol 0 Terminal X5/A4
C0121 OH7 limit 150 45 {1 °C} 150 Setting of the operating
temperature for monitoring OH7
z Only for KTY at X8
z Monitoring OH7 is configured
in C0584
6.6-10
See System
Manual
(extension)