Configuration
Code table
8
8.3
8.3-28
EDSVF9333V EN 3.0-06/2005
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0465
→ Selection list 5
Function block - processing list
z Defining the sequence in
which the function blocks are
to be processed internally
Æ Depending on C0005.
Changing C0005 loads
assigned processing list
Æ The displayed values apply to
C0005 = 1000
z After changing the signal flow,
adapt the processing list in any
case. Otherwise the controller
may use the wrong signals!
z The function blocks DIGIN,
DIGOUT, AIF-IN, CAN-IN, and
MCTRL are always processed
and do not have to be entered
in the list
1 FB list 200 DFIN
2 FB list 0
3 FB list 50 AIN1
4 FB list 0
5 FB list 0
6 FB list 55 AIN2
7 FB list 0
8 FB list 0
9 FB list 10250 R/L/Q
10 FB list 0
... ... 0
14 FB list 0
15 FB list 5250 NLIM1
16 FB list 5050 NSET
... ... 0
19 FB list 5700 ANEG1
... ... 0
22 FB list 10650 CMP1
... ... 0
25 FB list 70 AOUT1
... ... 0
28 FB list 75 AOUT2
... ... 0
31 FB list 250 DFOUT
... ... 0
41 FB list 25000 AIF-OUT
42 FB list 20000 CAN-OUT
... ... ...
50 FB list 0
C0466 CPU T remain Remaining process time for
processing the function blocks
z Display only
C0469
Fct STP key 2
0 inactive Inactive
Determines the function which is
released when pressing on
the keypad
Changes are only active after
mains connection!
1 CINH Inhibit controller:
2 qsp Quick stop
C0470 0 {1} 255 Configuration of free control
codes for digital signals
z The data words C0470 and
C0471 are in parallel and are
identical.
1 FCODE 8 Bit 0 FCODE bit 0-7
2 FCODE 8 Bit 0 FCODE bit 8-15
3 FCODE 8 Bit 0 FCODE bit 16-23
4 FCODE 8 Bit 0 FCODE bit 24-31
C0471 Configuration of
input
FCODE 32 Bit
0 0 {1} 4294967296 Free control code for digital
signals
z The data words C0470 and
C0471 are in parallel and are
identical.