Commissioning
Acceleration, deceleration, braking, stopping
Speed range
6
6.10
6.10.2
6.10-3
EDSVF9333V EN 3.0-06/2005
6.10.2 Setting acceleration times and deceleration times in speed mode
The acceleration and deceleration times determine the controller response
time after a setpoint change.
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0012 TIR (ACC) 5.00 0.00 {0.01 s} 9999.90 Acceleration time T
ir
of the main
setpoint
z Refers to speed change
0 ... C0011
6.10-3
C0013 TIF (DEC) 5.00 0.00 {0.01 s} 9999.90 Deceleration time T
if
of the main
setpoint
z Refers to speed change
0 ... C0011
ƒ The acceleration and deceleration times refer to a speed change from
0min
-1
to the max. speed set in C0011.
ƒ Calculate the times T
ir
and T
if
, which you can set under C0012 and
C0013.
n [min
-1
]
C0011
t
ir
t
if
t
T
ir
T
if
n
2
n
1
0
9300vec098
Fig. 6.10-2 Acceleration and deceleration times
T
ir
= t
ir
C0011
n
2
n
1
t
ir
and t
if
are the desired times for the change
between n
1
and n
2
T
if
= t
if
C0011
n
2
n
1
Note!
If the acceleration and deceleration times are set too short, and
under unfavourable operating conditions, the controller can be
switched off with TRIP OC1 or OC3. In these cases, the
acceleration and deceleration times must be set so that the drive
can follow the speed profile without I
max
reaching a drive
system.
Description