Configuration
Function blocks
Master frequency processing (DFSET)
8
8.2
8.2.5
8.2-24
EDSVF9333V EN 3.0-06/2005
Stop!
When the synchronisation via the terminals X5/E4 and X5/E5
(C0532 = 2) is activated, these terminals must not contain any
other signal connections.
When selecting a basic configuration via C0005, the terminals
contain a basic setting.
Selection of synchronisation
C0532=1(zeropulse) Thesynchronisationisperformedonthezerotrackofthe
digital frequency input X9 and the zero track of the feedback
system set under C0490.
C0532=2(touchprobe) The synchronisation is performed using the t erminals X5/E4
(actual pulse) and X5/E5 (setpoint pulse).
Touch probe initiators can have delay times which cause a speed-dependent
phase offset.
Set the correction for the phase offset under C0429.
C0429 = 16384 ⋅ Correction value
The correction value for the phase offset can be obtained from t he data
sheet of the initiator or contact the manufacturer.
Synchronisation modes
C0534 Synchronisation mode Note
0Inactive Function inactive
1 Continuous synchronisation with
correction in the shortest possible way
2 Continuous synchronisation with
correction in the shortest possible way
After a LOW-HIGH signal to
DFSET-0-pulse, the zero track is
synchronised once
10 Onesynchronisation.Aphasedeviationis
corrected in the shortest possible way.
11 Onesynchronisation.Aphasedeviationis
corrected in CW direction.
12 Onesynchronisation.Aphasedeviationis
corrected in CCW direction.
13 Single synchronisation. A phase difference
is determined between setpoint pulse and
actual pulse and is corrected to the
corresponding direction of rotation
according to the sign.
ƒ During synchronisation, DFSET-ACK i set to HIGH.
Note!
Drive synchronisation is only reasonable if the controller is
operated with incremental encoder feedback and the calculated
following error is used for correcting the speed setpoint. The
following error is output to DFSET-PSET.
Synchronising to zero track or
touch probe