Technical data
Operation with increased rated power
Rated data for 400 V mains voltage
3
3.3
3.3.1
3.3-3
EDSVF9333V EN 3.0-06/2005
Typical motor power
Three-phase asynchronous motor
(4-pol.)
P
r
[kW] 55 75 90 110
P
r
[hp] 74 100 120 148
9300 vector type EVF9330 EVF9331
4)
EVF9332 EVF9333
4)
Mains voltage U
mains
[V] 3/PE AC 320 V - 0 % ... 440 V + 0 % ; 45 Hz - 0 % ... 65 Hz + 0 %
Alternative DC supply U
DC
[V] DC 460 V - 0 % ... 740 V + 0 %
Data for operation on 3/PE AC 400 V or DC 565 V
Rated mains current with mains
choke/mains filter
I
mains
[A] 97.0 119 144 185
OutputpowerU.V,Wwithswitching
frequency 2 and 4 kHz
S
N
[kVA] 74.8 91.5 110 142
Output power +U
DC
,-U
DC
1)
P
DC
[kW] 0.0 0.0 13.1 20.6
Rated output current
with switching
frequency
2and4kHz I
r
[A] 100 135 159 205
8/2 kHz
3)
I
r
[A] 100 135 159 205
Max. permissible
output current for
60 s at a switching
frequency
2)
2and4kHz I
max
[A] 134 165 225 270
8/2 kHz
3)
I
max
[A] 134 165 225 270
Output voltage with mains
choke/mains filter
U
M
[V] 3~0...approx.94%U
mains
/ 0 ... 600 Hz
Power loss (operation with I
N
) P
v
[W] 1350 1470 2100 2400
Required mains choke Type
ELN3-0027H105 ELN3-0022H130 ELN3-0017H170 ELN3-0014H200
Dimensions
H [mm] 510 591 680 680
b [mm] 340 340 450 450
T [mm] 285 285 285 285
Earth [kg] 36.0 38.0 70.0 70.0
Bold print = Lenze setting
1)
Power supplied by the DC bus when operating with power-adapted motor
2)
Currents for periodic load change: 60 s of overcurrent time with I
max
and 120 s of base load time
with 75 % I
N
3)
Operation with automatic switching frequency reduction. When the max. permissible output
current is exceeded, the switching frequency is reduced to 2 kHz.
4)
Max. permissible ambient temperature during operation: + 35 °C