Configuration
Function blocks
Master frequency ramp-function generator (DFRFG)
8
8.2
8.2.4
8.2-17
EDSVF9333V EN 3.0-06/2005
The profile generator can accept a phase difference between the set phase
and the actual phase of up to ±2140000000 inc (= 32000 revolutions).
ƒ A limit value can be set for the permissible phase difference via C0754.
ƒ If the limit value is reached, DFRFG1-FAIL is set to HIGH and the value is
saved.
ƒ DFRFG1-FAIL is only set to LOW with DFRFG1-RESET = HIGH.
Monitoring the phase