MTS 793 Controller Hardware
FlexTest GT Controller Connections
136
Do not interrupt Model 493.10 Chassis power when you are
programming another controller. A power interrupt may cause the
external controller to react to a zero command and move the actuator
unexpectedly.
Ensure power cannot be removed accidently while a test is in progress.
For more detailed information about analog I/O connections, see
“Analog I/O Connections” on page 103.
407 Controller
Ch 1
Ch 2
Ch 3
Ch 4
Ch 5
Ch 6
m
J11
(Ch 1-4)
J12
(Ch 5-6)
493.77
Filtered In
PN 044-632-0XX
Ch 1
Ch 2
Ch 3
Ch 4
Ch 5
Ch 6
m
J11
(Ch 1-4)
J12
(Ch 5-6)
493.76
Analog Out
493.76 Analog Out
This module includes 6
BNC connectors that
provide analog outputs
from a Model 493.46 D/A
mezzanine card.
Six analog outputs are
available with each D/A
mezzanine card installed on
the Model 493.40 I/O
Carrier module.
493.77 Filtered
Analog Input
This module includes 6
BNC connectors that
provide filtered analog
inputs to a Model
493.45 A/D mezzanine
card.
Six analog inputs are
available with each A/D
mezzanine card
installed on the Model
493.40 I/O Carrier
module.
Transition modules on the
rear panel of the Model
493.10 chassis are used for
analog inputs and outputs.
Single 407 Controller Connections