5 Advanced Operations
5 - 56
E5@C-T Digital Temperature Controllers User’s Manual (H185)
z Related Parameters
Enabling Waiting and Setting a Wait Band
Enabling and Disabling Waiting with an Event Input
You can repeatedly execute the same program.
• Setting program repetitions automatically restarts execution of the same program from segment 0
after the final segment is executed. You can set the number of program repetition to up to 9,999 rep-
etitions. Set the number of program repetitions in the Program Repetitions parameter (Program Set-
ting Level).
• The number of executions will be one more than the specified number of program repetitions.
• If the Program Repetitions parameter is changed to a smaller number during program operation, the
currently executing program will be executed to the end and then the program will stop.
z Related Parameters
You can specify the number of the next program to execute when execution of a program is completed.
• When the last segment is executed, execution will move to segment 0 of the program specified in the
Program Link Destination parameter (Program Setting Level). Operation will be ended if the Program
Link Destination parameter is set to END.
• If a program repeat operation is also set, the program link will start after the program repetition
operation has been completed.
• If the current program number is specified in the Program Link Destination parameter, the program
will be repeated indefinitely.
• After all programs have been executed, operation will be according to the setting for the Operation
End Operation parameter.
z Related Parameters
Parameter
name
Display Setting range Default Level
Wait Band wt-b
Temperature input: 0.1 to 999.9°C or °F,
Analog input: 0.01 to 99.99
off
Adjustment Level
Parameter
name
Display Setting range Default Level
Event Input
Assignment
eV-1
eV-2
eV-3
eV-4
eV-5
eV-6
wait: Wait Enable/Disable
Event Input
Assignment 1:
rr-1
Event Input
Assignment 2:
adv
Event Input
Assignment 3 to
6: none
Initial Setting
Level
5-15-5 Program Repetition
Parameter name Display Setting range Default Level
Program Repetitions rpt 0 to 9999 0 Program Setting Level
5-15-6 Program Links
Parameter name Display Setting range Default Level
Program Link Destination link end, 0 to 7end Program Setting Level

Table of Contents

Other manuals for Omron E5*C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C Series and is the answer not in the manual?

Omron E5*C Series Specifications

General IconGeneral
BrandOmron
ModelE5*C Series
CategoryController
LanguageEnglish

Related product manuals