3 Select a target device to open a connection from the Toolbox. Drag and drop it on the connec-
tion list for either Port 1 or Port 2 to add the target device and default connection.
l
Setting the Target Device IP Address
Use the following procedure to set the address of the target device to open CIP Safety connection.
1 Select a target device in the connection list and right-click on it. Click the Edit Menu.
The target device settings pane is displayed.
Change the displayed settings according to the actual target device settings.
The settings depend on a type of the target device as shown in the following table.
Target device type Setting Items
Safety CPU Unit IP Address: Specify the IP address for the built-in EtherNet/IP port of the
NX102 CPU Unit.
NX Unit Number: Specify the NX Unit number of the Safety CPU Unit.
Safety network number (NX bus): Specify the SNN in the TUNID that is set
in the target Safety CPU Unit.
Other EtherNet/IP Safety devices
IP Address: Specify the IP address of the target device.
5 System Configuration and Setup
5 - 16
NX-series Safety Control Unit User's Manual (Z930)