Event code Event name Meaning Assumed cause
Level
Reference
M
a
j
P
rt
M
i
n
O
b
s
I
n
f
o
35200001 hex
[NX-SL5£££]
FSoE Mas-
ter Connec-
tion Not Es-
tablished Er-
ror
FSoE communica-
tions were not estab-
lished with the FSoE
slave.
• The FSoE communications
settings are not correct, the
FSoE slave is not in the cor-
rect status, etc.
• The FSoE slave for FSoE
communications is not con-
nected.
• The FSoE slave set in the NX
Unit Mounting Setting for FSoE
communications is disabled.
• The version of the FSoE slave
to be communicated is older
than the configured version.
¡
page
12 - 34
12 Troubleshooting
12 - 18
NX-series Safety Control Unit User's Manual (Z930)