EasyManuals Logo
Home>Omron>Controller>NX-SID Series

Omron NX-SID Series User Manual

Omron NX-SID Series
626 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #83 background imageLoading...
Page #83 background image
Item Specification
Operating environment Ambient operating tem-
perature
0 to 55°C
Ambient operating humid-
ity
10% to 95% (with no condensation or icing)
Atmosphere Must be free from corrosive gases.
Ambient storage tempera-
ture
−25 to 70°C (with no condensation or icing)
Altitude 2,000 m max.
Pollution degree Pollution degree 2 or less: Conforms to JIS B 3502
and IEC 61
131-2
Noise immunity Conforms to IEC 61
131-2, 2 kV (power supply line)
Insulation class CLASS III (SELV)
Overvoltage category Category II: Conforms to JIS B 3502 and IEC 61131-2
EMC immunity level Zone B
Vibration resistance Conforms to IEC 60068-2-6
5 to 8.4 Hz with amplitude of 3.5 mm
8.4 to 150 Hz, acceleration of 9.8 m/s
2
100 min. in each X, Y
, and Z directions (10 sweeps of
10 min. each = 100 min. total)
Shock resistance Conforms to IEC 60068-2-27
147 m/s
2
, 3 times in each X, Y, and Z directions
Isolation method Photocoupler isolation
Insulation resistance 20 MΩ
between isolated circuits (at 100 VDC)
Dielectric strength 510 VAC between isolated circuits for 1 minute at a
leakage current of 5 mA max.
Installation method DIN Track (IEC 60715 TH35-7.5/TH35-15)
Individual Specifications
This section provides the individual specifications of the Safety Input Unit.
l
Datasheet Items for Safety Input Unit
The following table gives the meaning of the datasheet items for the Safety Input Units.
Item Specification
Number of safety input points This is the number of safety input points on the Unit.
Number of test output points This is the number of test output points on the Unit. The test output points
are used with the safety input terminals.
Internal I/O common This is the polarity that the Unit uses to connect to input devices.
Rated input voltage This is the rated input voltage of the Unit.
OMRON Special Safety Input De-
vices
This tells whether the Unit supports the connection of OMRON Special
Safety Input Devices (D40A Non-contact Door Switches, E3FS Single
Beam Safety Sensors, etc.).
Number of safety slave connec-
tions
This is the number of slave connections that the Unit can have through
FSoE. Y
ou can perform communications with one FSoE master device per
connection.
I/O refreshing method This is the I/O refreshing method for the Unit.
2 Specifications
2 - 17
NX-series Safety Control Unit User's Manual (Z930)
2-2 Safety Input Unit
2
2-2-1 Models and Specifications

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX-SID Series and is the answer not in the manual?

Omron NX-SID Series Specifications

General IconGeneral
BrandOmron
ModelNX-SID Series
CategoryController
LanguageEnglish