Parameters
List of Parameters
1-18
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Description: Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value: 0: Ready
1: Quick commissioning
2: Power unit commissioning
3: Motor commissioning
5: Technological application/units
15: Data sets
29: Only Siemens internal
30: Parameter reset
39: Only Siemens internal
49: Only Siemens internal
Dependency: Refer to: r3996
Notice: When the parameter is reset to a value of 0, short-term communication interruptions may occur.
Note: The drive can only be powered up outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Once the Control Unit has been booted up for the first time, the motor parameters suitable for the power unit have
been defined, and the control parameters have been calculated accordingly, p0010 is automatically reset to 0.
p0010 = 3 is used for the subsequent commissioning of additional drive data sets (creating data sets: see p0010 =
15).
p0010 = 29, 39, 49: Only for internal Siemens use!
p0010 Drive commissioning parameter filter / Drv comm. par_filt
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 49 1