EasyManuals Logo

Siemens SINAMICS G120 User Manual

Siemens SINAMICS G120
732 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #576 background imageLoading...
Page #576 background image
Function diagrams
Setpoint channel
2-576
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Fig. 2-69 3080 – Ramp-function generator selection, status word, tracking
- 3080 -
Function diagram
87654321
FP_3080_97_51.vsd
Setpoint channel
G120 CU230P-2
13.12.2010 V4.4
Ramp-function generator selection, status word, tracking
[6030.1]
[3060.8]
[3070.8]
1
Hochlaufgeber-Zustandswort
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Bit
[3060.8]
[3070.8]
0
1
1
0
0
1
0
0
1
0
Hochlaufgeber freigeben (von STW Ablaufsteuerung)
r0898.4
<2>
+
+
[2501.7]
[2501.7]
x
y
+
+
<1>
<2>
xy
[3080.8]
[3050.8]
[2522.7]
[3060.1]
[3070.3]
<4>
<2>
<4>
<1>
(p2148)
t
x,y x
y
t
x,y x
y
T1
T1
[3060.8]
[3070.8]
<5>
<5>
Ramp-function generator selection
From the basic ramp-function generator
From the expanded ramp-function generator
n_set_4
n_set_5
Interpolator
Interpolator
Ramp-function generator tracking
Ramp flattening-off
Ramp-function generator status word
Ramp-up active
Ramp-down active
Ramp-function generator active
Ramp-function generator set
Ramp-function generator held
Ramp-function generator tracking active
Maximum limiting active
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
For p1145 > 0, ramp-function generator tracking is activated when the torque limiting
responds. This means that the speed controller output only exceeds the torque limit by a
deviation that can be set via p1145.
For OFF1/OFF3, the ramp-function generator ramp is active. The ramp-function generator is
set to the setpoint (r1170)) and stops the drive with the ramp-downtime (p1121 or p1135).
STW1.4 (enable ramp-function generator) is effective while the drive is stopped via the
ramp-function generator. Depending on the p1115, the basic ramp-function generator [3060]
or the extended ramp-function generator [3070] is effective.
Behavior of the response ramp of the torque limiting:
p1145 = 0.0: No ramp-function generator tracking. The ramp-function generator ramp is no longer in the range of the
frequency actual value.
p1145 = 1.0: The ramp-function generator ramp remains as close as possible to the speed actual value.
p1145 > 1.0: The ramp-function generator ramp is steeper than for p1145 = 1.0 (higher "speed following error").
The value is displayed correctly only with r0899.2 = 1 (operation enabled)
ZSW n_ctrl
r1407
r1407
.7
RFG selection
p1115
STW seq_ctrl
r0898
r0898
.6
n_ctrl n_set 1
(0)
p1155 [C]
n_ctrl n_set 2
(0)
p1160 [C]
r1150
RFG n_set at outp [1/min]
RFG track intens
0.0 ... 50.0
p1145 [D] (0.0)
r1169
n_ctrl n_set 1/2 [1/min]
r1170
n_ctrl setp sum [1/min]
RFG ZSW
r1199
r1199
RFG ZSW
r1199
r1199
.2
RFG ZSW
r1199
r1199
.5
If technology controller is activated (p2200 > 0, p2251 = 1) connected with r2294.
<3>
<3>

Table of Contents

Other manuals for Siemens SINAMICS G120

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120 and is the answer not in the manual?

Siemens SINAMICS G120 Specifications

General IconGeneral
Power Range0.37 kW to 250 kW
Output Voltage0 V to Input Voltage
Frequency Range0 Hz to 650 Hz
Enclosure RatingIP20, IP21, IP55
Control ModesV/f control, vector control, servo control
Protection FeaturesOvervoltage, undervoltage, short circuit
Communication InterfacesPROFIBUS, PROFINET, Modbus RTU
Operating Temperature-10°C to +50°C
Cooling MethodAir cooling
Input Voltage200 V to 240 V, 380 V to 480 V, 500 V to 690 V

Related product manuals