Function diagrams
Internal control/status words
2-552
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Fig. 2-46 2505 – Control word, setpoint channel
- 2505 -
Function diagram
87654321
FP_2505_97_51.vsd
Internal control/status words
G120 CU230P-2
13.12.2010 V4.4
Control word, setpoint channel
11
12
13
14
15
9
10
8
7
6
5
4
3
2
1
0
r1198.3
r1198.5
r1198.6
r1198.11
r1198.13
r1198.14
r1198.2
r1198.1
r1198.0
r1198.15
(0)
n_set_fixed Bit 0
p1020 [C]
(0)
n_set_fixed Bit 1
p1021 [C]
(0)
n_set_fixed Bit 2
p1022 [C]
(0)
n_set_fixed Bit 3
p1023 [C]
(0)
Mop raise
p1035 [C]
(0)
Mop lower
p1036 [C]
(0)
Bypass RFG
p1122 [C]
Control word, setpoint channel (r1198)
1 = Fixed setpoint, bit 0
1 = Fixed setpoint, bit 1
1 = Fixed setpoint, bit 2
1 = Fixed setpoint, bit 3
Reserved
1 = Inhibit negative direction of rotation
1 = Inhibit positive direction of rotation
Reserved
Reserved
Reserved
Reserved
1 = Setpoint inversion
Reserved
1 = Motorized potentiometer, raise
1 = Motorized potentiometer, lower
1 = Bypass ramp-function generator
To fixed speed setpoints [3010.2]
To fixed speed setpoints [3010.2]
To fixed speed setpoints [3010.2]
To fixed speed setpoints [3010.2]
To direction of rotation limiting and
direction of rotation reversal [3040.3]
To direction of rotation limiting and
direction of rotation reversal [3040.5]
To direction of rotation limiting and
direction of rotation reversal [3040.2]
To the motorized potentiometer [3020.1]
To the motorized potentiometer [3020.1]
To the setpoint channel [3060.1] [3070.3]
STW setpoint chan
r1198
r1198
Bit No.
(1)
Inhib neg dir
p1110 [C]
(0)
Inhib pos dir
p1111 [C]
(722.1)
Setp inv
p1113 [C]