NetSure
â„¢
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
SAMPLES
TL1 Message Samples
These samples use the system identifier (<tid>): Lorain.
Autonomous Message on Connect
When the Telnet connection is established, the controller will provide the active alarms in an autonomous message. In this example,
there are two alarms.
Lorain 15-09-24 13:47:00
*C 1 REPT ALM EQPT
"PowerSystem:CR,Alarm,SA,09-24,13-45-31,,,1,,1-MIN:\"CAN Communication Failure\","
"PowerSystem:CR,Alarm,SA,09-23,13-39-43,,,1,,1-DAY:\"SPD\","
;
<
Activate User
The ACT-USER request (example: ACT-USER::drw:51::1_2345; for username drw with password 1_2345) can be used to log in. The
controller will not respond to requests unless a user is logged in (or the controller is configured with auto-login). The controller responds
with this message:
Lorain 15-09-24 15:29:14
M 51 COMPLD
/* This is a private computer system.
Unauthorized access may result in criminal prosecution */
;
<
Cancel User
The CANC-USER request (example: CANC-USER:Lorain:drw:16; for username drw) can be used to log-out the current user. The controller
responds with this message:
Lorain 15-09-25 08:18:04
M 16 COMPLD
;
<
Retrieve Header
The RTRV-HDR request (example: RTRV-HDR:::20;) can be used to ‘ping’ the controller to confirm that there is a connection established.
The controller responds with this message:
Lorain 15-09-25 08:17:57
M 20 COMPLD
;
<
Retrieve Equipment
The RTRV-EQPT request (example: RTRV-EQPT:Lorain:SYSTEM:40;) can be used to get information about the controller. The controller
responds with this message:
Lorain 15-09-25 08:17:55
M 40 COMPLD
"SYSTEM:M830B::SWVER=1.00,CURSWVER=1.1.41T04,:IS-NR,"
;
<
The controller type is M830B. The configuration is version 1.00. The software version is 1.1.41T04.