NetSure
â„¢
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
[199]
RETRIEVE-ALARM
(RTRV-ALM-{EQPT|ALL})
Referenced In: TR-NWT-000833, Issue 5; pg. 4-205
General Description: Instructs the NE (NCU) to send the current state of its alarm conditions associated with one or more equipment
units, facilities, etc. within the NE (NCU).
NCU Access Level: any access level
Input Format:
RTRV-ALM-{EQPT|ALL}:
[<tid>]:<aid>:<ctag>::[<ntfcncde>],[<condtype>], [<srveff>],[<locn>],[<dirn>][,<tmper>];
NOTE: The command code modifier of COM is not supported. If specified, an error response with the error code ICNV is returned.
<aid>
A value of ALL requests retrieval of alarm conditions for all AIDs of the type defined by the command code modifier. Use of
the command code modifier ALL results in retrieval of all alarm conditions in the NE (NCU).
If the command code modifier is ALL, the <aid> must be ALL. A <null> value is not permitted for this parameter.
<ntfcncde>
This is the notification code associated with the alarm conditions being retrieved. Valid values for this parameter are as
follows:
CR critical alarm
MJ major alarm
MN minor alarm
<null> request retrieval of alarm conditions for all of the above codes
<condtype>
This is the condition type of alarm conditions to be retrieved. A <null> value causes all conditions classified as alarm
conditions to be retrieved.
<srveff>
This is the effect on service caused by the alarm condition. Valid values for this parameter are as follows:
SA service-affecting condition
NSA nonservice-affecting condition
<null> request retrieval of alarm conditions for both of the above codes
<locn>
This is the location of the alarm condition. This parameter does not apply to this application. A <null> value is the only
value which is accepted for this parameter. If any other value is received for this parameter, an error response is returned
with the error code INUP.

Table of Contents

Other manuals for Vertiv Netsure

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Netsure and is the answer not in the manual?

Vertiv Netsure Specifications

General IconGeneral
BrandVertiv
ModelNetsure
CategoryControl Unit
LanguageEnglish

Related product manuals