*1: For non-redundant configuration, used to cover the slot at right-hand side of the single processor module.
*2:
Used to cover the empty I/O module slot.
*3: Required if the safety nodes are used.
n
Wide Range Temperature Type Safety Control Unit for V net
The components of the wide range temperature type safety control unit (Model: SSC10S-F/
SSC10D-F) are shown in the following figure.
This type of control unit consists of the standard type control unit and cooling fan unit so as to
work in a wider range of ambient environment (-20 to 70 deg. C).
4 5 6
1 2 3
RX+
RX- SG
Fan unit
Power input
terminal
Power supply unit
for fan unit
Grounding
terminal
Cable tray
V net coupler unit
*1: 1 UNIT=44.45 mm
Empty (1 UNIT) (*1)
Node fan unit (2 UNIT) (*1)
Utility unit (1 UNIT) (*1)
External interface unit
Base unit (5 UNIT) (*1)
GPS interface unit (option)
Processor
module
Power supply module
Such as Input/Output module
Figure 1.1-2 Configuration of Safety Control Unit (SSC10D-F)
Table 1.1-2 Model Names of Safety Control Unit Components (Wide Range Temperature Type)
Name
Wide range temperature type safety control unit
Single configuration
(SSC10S-F)
Duplexed configuration
(SSC10D-F)
Power supply module (100-120 V AC) SPW481 2pcs SPW481 2pcs
Power supply module (220-240 V AC) SPW482 2pcs SPW482 2pcs
Power supply module (24 V DC) SPW484 2pcs SPW484 2pcs
Processor module SCP401 1pcs SCP401 2pcs
Dummy cover (for processor module)(*1) T9083VB 1pcs - -
Dummy cover (for I/O module)(*2) SDCV01 as required SDCV01 as required
ESB bus coupler module(*3) SEC401 2pcs SEC401 2pcs
V net coupler unit AIP504 2pcs AIP504 2pcs
External interface unit (for wide range temperature
type safety control unit)
- 1pcs - 1pcs
Power supply unit for fan unit (100-120/220-240 V
AC)
S9159FA 2pcs S9159FA 2pcs
Power supply unit for fan unit (24 V DC) S9160FA 2pcs S9160FA 2pcs
Fan unit AIP602 2pcs AIP602 2pcs
Continues on the next page
<1.1 Configuration of Safety Control Unit > 1-4
IM 32Q06C10-31E 4th Edition : Jan.30,2015-00

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA SSC60D and is the answer not in the manual?

YOKOGAWA SSC60D Specifications

General IconGeneral
BrandYOKOGAWA
ModelSSC60D
CategoryControl Systems
LanguageEnglish

Related product manuals