Table 1.1-2 Model Names of Safety Control Unit Components (Wide Range Temperature Type) (T
able
continued)
Name
Wide range temperature type safety control unit
Single configuration
(SSC10S-F)
Duplexed configuration
(SSC10D-F)
GPS interface unit (option) - 1pcs - 1pcs
*1: For non-redundant configuration, used to cover the slot at right-hand side of the single processor module.
*2:
Used to cover the empty I/O module slot.
*3: Required if the safety nodes are used.
n
Standard Type Safety Control Unit for Vnet/IP
The components of the standard type safety control unit for Vnet/IP (Model: SSC50S-S/
SSC50D-S) are shown in the following figure.
The operating temperature range for the standard type safety control unit for Vnet/IPis –20 to
40 deg. C. Be sure to use it within the range.
Processor module
Power supply module
Utility unit (1 UNIT) (*1)
Base unit (5 UNIT) (*1)
External interface unit
Grounding
terminal
Cable tray
*1: 1 UNIT=44.45 mm
Such as Input/Output module
Figure 1.1-3 Configuration of Safety Control Unit for Vnet/IP (SSC50D-S)
Table 1.1-3 Model Names of Safety Control Unit for Vnet/IP Components (Standard Type)
Name
Standard type safety control unit for Vnet/IP
Single configuration
(SSC50S-S)
Duplexed configuration
(SSC50D-S)
Power supply module (100-120 V AC) SPW481 2pcs SPW481 2pcs
Power supply module (220-240 V AC) SPW482 2pcs SPW482 2pcs
Power supply module (24 V DC) SPW484 2pcs SPW484 2pcs
Processor module SCP451 1pcs SCP451 2pcs
Dummy cover (for processor module) (*1) T9083VB 1pcs - -
Dummy cover (for I/O module) (*2) SDCV01 as required SDCV01 as required
ESB bus coupler module(*3) SEC401 2pcs SEC401 2pcs
External interface unit for standard type safety con-
trol unit
- 1pcs - 1pcs
*1: For non-redundant configuration, used to cover the slot at right-hand side of the single processor module.
<1.1 Configuration of Safety Control Unit > 1-5
IM 32Q06C10-31E 4th Edition : Jan.30,2015-00