EasyManuals Logo
Home>ABB>Controller>AC 800F

ABB AC 800F User Manual

ABB AC 800F
379 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #134 background imageLoading...
Page #134 background image
4 Cabling the AC 800F
4-68
Functional description of LD 800P
The RS485 interface of the LD 800P link device (Profibus DP) supports all baud rates
up to 12 Mbauds specified for Profibus DP in DIN 19245/ EN 50170. The baud rates
are software-configurable. The two PA interfaces are specified in accordance with
IEC 61158-2 and permit baud rates of up to 31.25 kbauds. Activities on either of the
DP/PA lines are indicated by so-called token LEDs. The communicated data are
checked for errors, and detected errors are indicated. A separate power conditioner is
used for powering the PA lines. The termination of a PA line is realized on the power
conditioner.
Fig. 4-44 Connection diagram LD 800P

Table of Contents

Other manuals for ABB AC 800F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB AC 800F and is the answer not in the manual?

ABB AC 800F Specifications

General IconGeneral
BrandABB
ModelAC 800F
CategoryController
LanguageEnglish

Related product manuals