4 Cabling the AC 800F
4-4
When installing power supply module SA 811F, observe the following rules:
• Prior to connecting it to the mains voltage, first plug the power supply module
into the AC 800F and fasten it with screws.
• The power supply module has no mains switch, provide a double-pole one.
• It is recommended to usea2ATfusetoIEC/EN60127-2/V, ceramic cartridge
5 x 20 mm, high breaking capacity, melt index of at least 4 A
2
s e.g. Wickmann,
type 181.
Do not use fuses with a smaller melt index.
• Power cable: copper, cross-sectional area 0.75 mm
2
• Provide a functional grounding as described in Section 3.2.
• When using the AC 800F on a 115 - 230 V AC mains, make sure that it is
equipped with a SA 811F power supply module.
• Lay the mains cable separately (not too close to communication cables), as
seen in the following illustration.
Fig. 4-4 Laying cables of power supply module SA 811F
• Power supply module SA 811F has a 115 - 230 V AC input and outputs a 5 V
and 3.3 V voltage. It suppresses mains noise, acts as a buffer for up to 20 ms
with a minimum input voltage in case of a power failure, and generates a power-
fail signal.
• Power cable TK 808F with European plug is available for connection to a
European socket.
At present, the power supply module SA 811F can be run with CPU
board PM 803F only with software version 7.1 or higher.

Table of Contents

Other manuals for ABB AC 800F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB AC 800F and is the answer not in the manual?

ABB AC 800F Specifications

General IconGeneral
BrandABB
ModelAC 800F
CategoryController
LanguageEnglish

Related product manuals