4 Cabling the AC 800F
4-22
Connect the 10Base2 cable to ground on the 10Base2 module of every AC 800F, as
shown in Figure 4-12.
Protect the unsheathed metallic 10Base2 F-connectors and 10Base2 cable
connectors from any contact with ground or conductive parts of the building, e.g. by
using an insulating sleeve.
Proceed as follows:
• Strip off the insulating
sheath from one of the two
cables at about 2 cm (not
too close to the connector to
avoid sharp-edged cable
kinks).
• Fasten the braided cable
shield to the contact ledge on
AC 800F using clip TV 83xF
Fig. 4-12 Grounding the 10Base2 cable
4.2.7.3 Connecting 10Base2 nodes while the system is running
In many cases, the engineering station is only temporarily connected to the AC 800F.
There are three ways to connect and disconnect the engineering station while bus
operation is in progress:
1. Connection via 10Base2 F-connector
This is the easiest way to connect or disconnect a node to/from the network
without requiring additional material. Proceed as follows to disconnect the node:
Switch off
engineering station.
Disconnect 10Base2 F-
connector from
engineering station.
Avoid shorts with ground or
any conductive parts of the
building.

Table of Contents

Other manuals for ABB AC 800F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB AC 800F and is the answer not in the manual?

ABB AC 800F Specifications

General IconGeneral
BrandABB
ModelAC 800F
CategoryController
LanguageEnglish

Related product manuals