9 Technical Data of the AC 800F
9-2
9.2 Mechanical specifications
Test to DIN IEC 68, T. 2 - 27 and T. 2 - 6
Transportation
Shock 30 g/18 ms/18 shocks
Max. values for the individual modules. The values
are valid for assembled modules only if a
transportation restraint is used
Vibration, 3 * 5 cycles 2 g/0.15 mm/5 ... 150 Hz
Always put the AC 800F in its original packing for transportation to avoid damage.
Operation
Vibration, 3 * 2 cycles 2 g/0.075 mm/5 ... 150 Hz
For vibrations of more than 0.5 g the special mounting material for
vibration-resistant wall mounting has to be used!
9.3 Electromagnetic compatibility (EMC)
Meets the requirements of EMC regulation 89/336/EEC as of May 1989 or the
German EMVG (national EMC regulation) dated November 1992, respectively.
Complies with product standard EN 61326, Part1/01.98.
RFI suppression to EN 55022 / 4.1998;
(DIN VDE 0878 - Part 22 / 11.89, Class B)
EMI/RFI shielding to EN 50 082; VDE 0839 - Part 82-2
Test to EN61000-4; VDE 0847
with shielded communication cables
Parts 1 to 6,8,11, Degree 3, are met
ESD degree to EN 61131-2 / 1994
Degree ESD-3 is met
The industrial standard to NAMUR 21 / 8.98 is met.

Table of Contents

Other manuals for ABB AC 800F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB AC 800F and is the answer not in the manual?

ABB AC 800F Specifications

General IconGeneral
BrandABB
ModelAC 800F
CategoryController
LanguageEnglish

Related product manuals